JYH-B instrument transformer characteristic tester can measure the turns ratio, polarity and volt-ampere characteristics of the current transformers and voltage transformers. It has large power regulating transformer, step-up transformer and current-up device inside. The tester is widely used in the routine test of voltage and current transformers.
Output voltage and current | Load range | ||
Inbuilt step-up transformer | 0~2500V,
0~20A |
1A/2500V,
2A/1500V, 5A/600V, 10A/220V, 20A/30V |
|
Measuring accuracy | Accuracy of volt-ampere:0.5 class, accuracy of turns ratio measurement: 0.5 class (when secondary voltage≥50V, secondary current≥200mA) | ||
Inbuilt current-up device | 0-800A/1000A | 800VA | |
Precision of turns ratio measurement | ≤1% | ||
Power supply | AC220V,50/60Hz | ||
Environment temperature | -10℃~50℃ | ||
Dimension | 425m(L)*300mm(W)*290mm (H) | ||
Net weight | 26kgs |